Application
Application
- Rectangular VAV terminal units for use in ventilation and air conditioning systems
 - For control, inductor and shut-off tasks in the extract air area with high acoustic requirements
 - Integral attenuator
 - Closed-loop volume flow control using an external power supply
 - For variable or constant volume flow systems
 - Shut-off via override control by others
 - Can also be used for duct or room pressure control with suitable control components
 
Special features
- Integral attenuator with at least 26 dB insertion loss at 250 Hz
 - Hygiene tested and certified
 - Factory set-up or programming and aerodynamic function testing
 - Setting and subsequent parameterisation on the control component possible, separate setting device may be required
 
Nominal sizes
125, 160, 200, 250, 315, 400
Variants
- TVA: Extract air unit
 - TVA-D: Extract air unit with acoustic cladding
 - Units with acoustic cladding and/or secondary silencer Type TS for very demanding acoustic requirements
 - Acoustic cladding cannot be retrofitted
 
Parts and characteristics
- Ready-to-commission unit which consists of mechanical parts and control components
 - Averaging effective pressure sensor for volume flow rate measurement
 - Damper blade
 - Integral attenuator
 - Factory assembled control components complete with wiring and tubing
 - Aerodynamic functional testing on a special test rig prior to shipping of each unit
 - Set-up data is given on a label or volume flow rate scale affixed to the unit
 - High control accuracy even in case of unfavourable upstream conditions
 
Attachments
- EASY controller: Compact unit consisting of controller with potentiometers, effective pressure transducer and actuator
 - Compact controller: Compact unit consisting of controller with potentiometers, effective pressure transducer and actuator
 - Universal controllers: Controllers, differential pressure transducers and actuators for special applications
 - LABCONTROL: Control components for air management systems
 
Accessories
- Double lip seal (factory fitted)
 
Useful additions
- Secondary silencer Type TS
 
Construction features
- Rectangular casing
 - Spigot on the fan end suitable for circular ducts to EN 1506 or EN 13180
 - Spigot with groove for double lip seal
 - Connection on the room end suitable for ducts
 - Baffle plate is fitted after the damper blade for optimum aerodynamic performance
 - Position of the damper blade indicated externally at shaft extension
 - Thermal and acoustic insulation (lining)
 
Materials and surfaces
Casing and damper blade made of galvanised sheet steel
- Damper blade seal made of TPE plastic
 - Lining is mineral wool
 - Effective pressure sensor made of aluminium
 - Plastic plain bearings
 - Shaft and linkage made of galvanised steel
 
Variant with acoustic cladding (-D)
- Acoustic cladding made of galvanised sheet steel
 - Lining is mineral wool
 - Rubber elements for the insulation of structure-borne noise
 
Mineral wool
- To EN 13501, fire rating Class A1, non-combustible
 - RAL quality mark RAL-GZ 388
 - Non-hazardous to health thanks to being highly biosoluble in accordance with the Ordinance on Hazardous Substances and Note Q of the European Directive (EC) No. 1272/2008
 - Faced with glass fibre fabric as protection against erosion through airflow velocities of up to 20 m/s
 - Inert to fungal and bacterial growth
 
Standards and guidelines
Fulfils the hygiene requirements of
- EN 16798, Part 3
 - VDI 6022, Sheet 1
 - DIN 1946, Part 4
 - Further standards, guidelines in accordance with hygiene certificate
 
Casing leakage: NS 125 – 200
NS 250 – 400
Closed blade air leakage:
- EN 1751, Class 4
 - Meets the increased requirements of DIN 1946, Part 4, with regard to the acceptable closed damper blade air leakage
 
Maintenance
- Maintenance-free as construction and materials are not subject to wear
 
 